The pressure transmitters of Type 699 are switchable in pressure ranges and available with or without a display. A full version includes additional customer-specific adjustment options. Sensors specially developed for each pressure range enable physically accurate and long-term stable measurement. The variety of options allows for versatile use in HVAC technology as well as for fine measurements in industrial and medical fields.
Optionally with or without LCD display
Adjustable measuring ranges
Switchable output signals
Switchable characteristic curve (linear or square-rooted)
Zero-point reset button
Full scale value adjustable by the customer
Attractive price-performance ratio
Application possible in overpressure and vacuum ranges
Easy installation. Mounting bracket for wall or ceiling mounting integrated into the housing
Product feature
Pressure measuring range
-1 ... 50 mbar (Relative and difference)
Response time
<20 ms
Load change
<10 ms
Display
LCD display (2 lines, each with 8 alphanumeric digits); LCD display (Additional 30 mA current consumption with backlighting); Modbus module (RTU RS-485)
Setting range
The zero point can be reset using the reset button; The end value can be set via the DIP switch and also using the turbopoti
Adjustability
Depending on the variants ordered, various parameters can be configured by the user (see variant plan)
Sensor weight
90; 100 g
Field of application
Media
Air; Gas
Medium temperature
0 ... 70 °C
Permissible overload on one side P1
50 mbar (Application in the overpressure range); 100 mbar (Application in the overpressure range); -4 mbar (Application in the negative pressure range)
Permissible overload on one side P2
4 mbar (Application in the overpressure range); -50 mbar (Application in the negative pressure range); -1100 mbar (Application in the negative pressure range)
Bursting pressure
2 x overload (at room temperature); 1.5 x overload (at 70°C)
Ambient condition
Ambient temperature
0 ... 70 °C
Storage temperature
-10 ... 70 °C
Condensation
no condensation
Material
Housing with media contact
Polycarbonate PC
Membrane with media contact
Silicone
Measuring element with media contact
Ceramic Al2O3 (96 %)
Electrical data
Current consumption
<30 mA
Inverse-polarity protection
Short-circuit and reverse polarity protected. Each connection against each other with max. supply voltage.
Electrical connection
Screw terminals for wires and stranded wires up to 1.5 mm2; Cable bushings with integrated strain relief PG11