Visit
Official Website

EC Instruments & Engineering Sdn Bhd
46, Jalan Seri Austin 3/55,
Taman Seri Austin,
81100 Johor Bahru,
Johor, Malaysia.
+607-2870393
EC Instruments & Engineering Pte Ltd
50, Tuas Ave 11, #03-03,
Singapore 639107.
+65-96312280
+65-67740200
terry@ecinstruments.net
+6596312280

Ipoh Office
29, Laluan Bg Perdana 20, Taman Batu Gajah Perdana, 31550 Pusing, Perak, Malaysia.
terry@ecinstruments.net
+601110688201

TV500L-100-5 Isolating Signal Converter

Previous 4 / 9 Next


Download Files

TV500L-100-0.pdf (583.27 KB)
Technical data

Power supply
Supply voltage : 230 V AC ± 10 % or 24 V DC ± 15 %
Frequency AC : 47..63 Hz
Power consumption : < 3 VA (at 24 V DC, 80 mA)
Operating temperature : -10..+50 °C
CE-conformity : EN 55022, EN 60555,
IEC 61000-4-3/4/5/11/13
EMC : EN 61326-1:2013; EN 60664-1:2007
 
Inputs
Current : ± 20 mA or 0/4..20 mA selectable,
Ri = 43 Ω, overload max. 100 mA
Voltage : ± 10V or 0/2..10 V selectable,
Ri = 40 kΩ, overload max. 100 V
Start value : adjustable ± 1.5 %
End value : adjustable ± 1.5 %
Accuracy : < 0.3 %,
(single range adjustment < 0.1 %)
 
Output
Programmable output
Voltage → current : link between terminal 8 and 9
Current : 0/4..20 mA selectable, burden ≤ 400 Ω;
± 20 mA, burden ≤ 150 Ω
Burden error : < 0.1 % (RL = 0..200 Ω),
< 0.2 % (RL = 0..400 Ω)
Voltage : 0/2..10V selectable, load max. 10 mA;
± 10 V, load max. 5 mA
Rise time (T90) : < 40 ms
Case : standard case polycarbonate 8020 UL94V-1
acc. to DIN EN 60715:2001-09, TS35
Weight : approx. 200 g
Electrical connection : screw terminals, max. 2.5 mm²
Protection class : case IP30,
terminals IP20, acc. to BGV A3
Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Ship to Name  
Shipping Address  
Messages*  
   

Subscribe Newsletter